Power transformers are critical assets in electrical power systems, and ensuring their reliability and longevity is paramount to maintaining the stability of power grids. One of the most significant threats to transformer health is internal degradation, which can manifest through electrical and thermal stresses. Dissolved Gas Analysis (DGA) is a widely accepted method for diagnosing transformer health by detecting specific gases dissolved in the transformer oil. These gases, including hydrogen, methane, ethylene, and others, are by-products of insulation breakdown and oil degradation, which occur due to faults like partial discharge, arcing, and overheating. While traditional methods for interpreting DGA data, such as the Rogers Ratio, Duval Triangle, and Key Gas Method, have been valuable, they often rely on fixed thresholds or expert judgment, which can limit their accuracy and scalability. Recent advancements in machine learning (ML) offer a promising alternative by enabling data-driven approaches that can identify complex patterns and relationships within DGA features. This report presents an ML approach for power transformer health assessment, employing the Kolmogorov-Arnold Network (KAN) model, a state of the art ML model that is a variant of the conventional feed forward neural network. The study leverages DGA data to train and evaluate the models, aiming to enhance accuracy in fault detection. KAN is used to capture the non-linear relationship and complexity within the DGA data, while Multilayer Perceptron (MLP) serves as a baseline for comparison. The results show the KAN model with 3 layers, with an RMSE of 0.0011 and R2 of ≈ 1.000 in independently reserved test data. PSO and Gauss-Newton approches were both implemented in which Gauss-Newton showed much better results.The result seem to suggest that local optimisation may be more applicable due to solution length and complex nature of solution subspace.